Kiosk-Type Substations
Self-contained, environmentally controlled metallic enclosures designed to house Medium Voltage (MV) switchgear, distribution transformers, and Low Voltage (LV) panels.
Manufactured in customizable configurations to fit available site space, these turnkey substations are fully assembled and factory-tested prior to delivery. They offer a reliable, weather-protected power distribution solution tailored to local grid standards and specific client requirements.

Key Highlights
Ideal Applications
Product Types


1. Compact Kiosk-Type Transformer Station
An all-in-one outdoor solution featuring three segregated compartments—with the MV and LV compartments positioned at opposite ends of the central transformer compartment:
Medium Voltage (MV) Compartment: Houses GIS, vacuum, or air-insulated switchgear with mechanical interlocks and cable termination access.
Transformer Compartment: Accommodates oil-immersed or dry-type transformers. Equipped with an integrated oil-containment sump (for oil-type units), adjustable transformer rails, internal lighting, and thermostat-controlled exhaust fans.
Low Voltage (LV) Compartment: Houses main incoming circuit breakers, outgoing distribution feeders, metering systems, and optional Power Factor Correction (PFC) panels.
2. Compact Kiosk-Type MV/LV Distribution Station
An all-in-one outdoor switching and distribution solution combining medium-voltage (MV) switchgear, auxiliary distribution equipment, and low-voltage (LV) distribution panels inside a single weather-protected, climate-controlled metallic enclosure.
Technical Specifications
Applicable Standards
| Standard | Description |
|---|---|
| IEC / EN 62271-202 | High-voltage / low-voltage prefabricated substations |
| IEC 62271-200 | AC metal-enclosed switchgear and controlgear (MV Switchgears) |
| IEC 60076 | Power and distribution transformers |
| IEC 60529 | Degrees of protection provided by enclosures (IP Code) |
| IEC 60721-1 | Classification of environmental conditions |
| NFPA 2001 / EN 15004 / ISO 14520 | Clean-agent fire extinguishing systems (FM-200) |
Design Criteria & Operating Conditions
| Parameter | Specification |
|---|---|
| Installation Environment | Outdoor |
| Maximum Altitude | Up to 1,000 m above sea level (Higher altitudes available per derating) |
| Ambient Temperature | -25°C to +55°C (Design baseline min -10°C; up to +55°C with A/C unit; extended ranges upon request) |
| Relative Humidity | 5% to 95% (Non-condensing) |
| Pollution / Ambient Class | Dirty Class 3 |
| Max Solar Radiation | 1,100 W/m² |
| Seismic Withstand (Earthquake) | 0.5 g Horizontal / 0.4 g Vertical |
| Wind Speed / Dynamic Pressure | 45 m/s (Wall design dynamic pressure: 2,500 N/m² / Pa) |
| Insulation Class | Up to 36 kV |
Mechanical & Structural Construction

General Enclosure & Protection
| Parameter | Specification |
|---|---|
| Degree of Protection | IP56 (MV Switchgear & LV Compartments) / IP23D (Transformer Compartment) |
| Mechanical Impact Resistance | IK10 |
| Enclosure Thermal Class | Class 10 / Class 20 (Per IEC 62271-202) |
| Fire Resistance Rating | Class A1 non-combustible materials / Class F90 (A-B) 90-minute fire resistance |
| Raised Flooring System | Complies with DIN 12825; distributed load-bearing capacity over 1 ton |
Base Frame & Structural Chassis
| Component | Material & Standard |
|---|---|
| Main Beams / Girders | NPU structural steel profiles — S275 JR (TS / EN 10025-2) |
| Secondary Girders | Hollow sections (EN 10210), IPE, UPN, and L profiles — S235 / S275 JR (TS / EN 10025) |
| Bottom Plate | 2 mm & 3 mm steel plate — S235 JR (EN 10025 / ASTM A283C / A570 Gr. 33, 36 eq.) |
| Base Frame Coating | Primed with secondary industrial black spray paint |
| Base Construction Method | Fully welded per TS / EN ISO 15607, ISO 4063, EN 287-1, EN 15609 |
Walls, Roof & Surface Finish
| Component | Specification |
|---|---|
| Main Enclosure Structure | 2 mm galvanized sheet steel (Aluzinc or Aluminum optional) with external bending and double-layer arrangement (TS / EN 10346) |
| Secondary Framing | Structural profiles as required — S235 / S275 JR (TS / EN 10025) |
| Assembly Method | Partially welded and rivet-mounted |
| Fasteners | Hex head bolts (DIN 931 Class 8.8 galvanized), hex nuts (DIN 934 Grade 8.8 galvanized), washers (DIN 125-A, DIN 7603 galvanized), and inox monobolt rivets (DIN 7337) |
| Surface Coating | Chemical surface cleaning followed by electrostatic epoxy-polyester powder coating — RAL 7035 (Class C2, thickness 65 ± 10 µm; custom colors available) |
Thermal Insulation (Double-Walled Roof & Panels)
Note: Available with Expanded Polystyrene (EPS) or non-combustible Rock Wool per TS / EN 13162 (Fire Class A1, Thermal Conductivity: 0.040 W/mK, Max Operating Temp: 750°C).
Walls: 40 mm Rock Wool / EPS double-layer arrangement
Bottom / Floor: 40 mm Rock Wool / EPS
Ceiling / Roof: 20 mm Rock Wool / EPS double-layer arrangement
Access Doors
Configuration: Double-leaf doors (~2,000 × 2,200 mm total; ~1,000 × 2,200 mm per leaf)
Hardware & Finish: Heavy-duty galvanized handles and hinges, integrated locking mechanism, and electrostatic powder-coated galvanized steel chassis and cover
HVAC, Air Conditioning & Ventilation System
Engineered to prevent condensation, remove internal heat dissipation from transformers and switchgear, and ensure reliable operation in ambient temperatures up to +55°C.
| Component / Parameter | Specification |
|---|---|
| Air Conditioning (A/C) Units | Industrial heavy-duty wall-mounted or rooftop split/packaged A/C units sized for internal heat loads in MV and LV compartments (N+1 redundant configuration available upon request) |
| Operating Ambient Rating | High-ambient tropicalized compressors rated for continuous operation up to +55°C |
| Natural & Forced Ventilation | Weatherproof louvers with washable G3/G4 dust and insect filters; thermostat-controlled high-airflow exhaust fans for transformer and auxiliary compartments |
| Anti-Condensation & Heating | Thermostatically and hygrostatically controlled space heaters inside MV/LV compartments to prevent moisture buildup in low temperatures or high humidity |
| Dampers & Pressure Relief | Gravity-operated or motorized fire/smoke dampers integrated with the fire suppression system, plus over-pressure relief flaps |
| Controls & Monitoring | Digital thermostat/hygrostat controllers with high-temperature alarm relays and remote SCADA monitoring contacts |
Electrical Auxiliaries, Fire Protection, Earthing & Lighting
Fire Detection & Suppression System (FM-200 / HFC-227ea)
Available as an integrated safety package across MV, LV, and Transformer compartments in compliance with NFPA 2001, EN 15004, and ISO 14520 standards.
| Component / Parameter | Specification |
|---|---|
| Extinguishing Agent | FM-200 (HFC-227ea) clean gas agent — electrically non-conductive, residue-free, and safe for sensitive electronic and switchgear equipment |
| Detection System | Cross-zoned addressable/conventional optical smoke detectors and rate-of-rise heat detectors |
| Control & Release Panel | Dedicated Fire Extinguishing Control Panel with battery backup, abort switch, manual release call point, and remote SCADA/alarm dry contacts |
| Discharge & Piping | Seamless high-pressure steel manifold, discharge nozzles engineered for uniform compartment coverage within 10 seconds, and pressure switches |
| Audio-Visual Alarms | Internal and external high-decibel electronic sirens, flashing strobes, and "Gas Discharged / Do Not Enter" warning signs |
| Safety Interlocks | Automatic shutdown of HVAC/A/C units and ventilation fans, closing of motorized fire dampers, and optional tripping of MV/LV main breakers prior to gas discharge |
Earthing & Equipotential Bonding
Main Earthing System: Electrolytic copper main earthing bar sized to station short-circuit withstand current and duration, complete with external grounding connection terminals.
Equipotential Bonding Conductor: Perimeter copper busbar (25 × 5 mm / 125 mm²), rated for 25 kA / 1 sec.
Protective Earthing Conductors: Minimum 35 mm² cross-section green/yellow V-90 PVC-sheathed copper cables with bolted structural connections for all electrical equipment.
Non-Energized Metal Parts: Doors, shutters, and control panels bonded to the grounding circuit via 16 mm² conductors.
Lighting & Power Outlets
Interior Ceiling Lighting: Industrial-grade fluorescent luminaires with integrated 180-minute emergency battery kit
Emergency Exit Lighting: 3-hour backup LED Exit Sign.
Service Receptacles: Industrial power sockets
Exterior Fixtures: Optional upon customer request.